Modifying UPS control parameters
ON-LINE UPS:
To open this option, select UPS control parameters from the UPS menu. The UPS Control Parameters
window pops up.
Read the table followed for detailed information.
Options Explanation
The limit value of the input
frequency
When the frequency of the utility power is out of this range, UPS will count
it abnormal and switch to battery supply.
The limit value of the bypass
voltage
When UPS supplies in bypass mode, if the utility voltage is out of this
range, UPS will cut off bypass output
Allow OFF-Key to enable /
disable audible warning when
UPS works on bypass
When Yes is enabled: UPS is supplied by bypass, users can turn off the
bypass audible alarm (beep once every 2 minutes) by pressing OFF button
on the UPS panel for one time, and pressing one more time to recover it.
When No is enabled: the “OFF” button on the UPS panel cannot be used
to control bypass audible alarm on/off.
Allow ON-Key to enable /
disable audible warning when
UPS works on battery mode
When Yes is enabled: UPS is supplied by batteries, users can turn off the
audible alarm (beep once every 4 seconds) supplied by batteries by
pressing “ON” button on the UPS panel for one time, and pressing one
more time the audible alarm can be turned on again.
When No is enabled: the “ON” button on the UPS panel cannot be used to
control the audible alarm supplied by batteries on/off.
Bypass audible warning When Yes is enabled: UPS is supplied by bypass, it is allowed to have
bypass audible alarm.
When Silent is enabled: UPS is supplied by bypass, it is not allowed to
have audible alarm, at this time the “OFF” button on the UPS panel cannot
turn on the bypass audible alarm.